增加高壓開關(guān)柜絕緣水平的方法

發(fā)布時間:2023-10-31 來源:http://www.26huojia.com/ 瀏覽量:

隨著電力系統(tǒng)的快速發(fā)展,高壓開關(guān)柜的安裝數(shù)量顯著增加。近年來,高壓開關(guān)柜的性能和質(zhì)量直接關(guān)系到高壓開關(guān)柜的故障統(tǒng)計數(shù)據(jù)顯示,由于絕緣缺陷、爬電、閃絡(luò)、小動物攀爬等絕緣問題,故障占總故障的30%。大多數(shù)舊運行開關(guān)柜不能滿足標(biāo)準要求的絕緣距離。在高潮或高海拔地區(qū)存在隱患。如果設(shè)備出現(xiàn)故障,一般認為是設(shè)備質(zhì)量差造成的。等級低,因此經(jīng)常努力提高設(shè)備指標(biāo)的水平。事實上,設(shè)備的絕緣水平也是一個重要問題。本文介紹了增加高壓開關(guān)柜絕緣水平的方法,有效地解決了高壓開關(guān)柜因絕緣問題而導(dǎo)致的設(shè)備故障。
With the rapid development of the power system, the number of high-voltage switchgear installations has significantly increased. In recent years, the performance and quality of high-voltage switchgear are directly related to the fault statistics of high-voltage switchgear. Statistics show that due to insulation defects, creepage, flashover, and small animal climbing, faults account for 30% of the total faults. Most old operating switchgear cannot meet the insulation distance required by national standards. There are hidden dangers in high tide or high-altitude areas. If the equipment malfunctions, it is generally believed to be caused by poor equipment quality. The level is low, so we often strive to improve the level of equipment indicators. In fact, the insulation level of equipment is also an important issue. This article introduces methods to increase the insulation level of high-voltage switchgear, effectively solving equipment failures caused by insulation issues in high-voltage switchgear.
長期以來,一些高壓開關(guān)柜制造商沒有嚴格執(zhí)行相關(guān)技術(shù)標(biāo)準,因此一些正在運行的開關(guān)柜中帶電體的相位和相位。相位和地面之間的空氣絕緣間隙大多在100~125mm之間。《高壓配電裝置設(shè)計技術(shù)規(guī)程》作為一種純空氣絕緣的電氣設(shè)備,明確規(guī)定10kV系統(tǒng)純空氣絕緣的小間隙為125mm。從交流耐壓試驗和事故分析的結(jié)果可以看出,10kV高壓開關(guān)柜中帶電體的相位和相位與地面之間的小空氣絕緣間隙小于125mm,容量發(fā)生事故。
For a long time, some high-voltage switchgear manufacturers have not strictly implemented relevant technical standards, so some operating switchgear cabinets have phases and phases of live parts. The air insulation gap between the phase and the ground is mostly between 100-125mm. The Technical Specification for Design of High Voltage Distribution Equipment, as a pure air insulated electrical equipment, clearly stipulates that the small gap for pure air insulation in 10kV systems is 125mm. From the results of AC voltage withstand test and accident analysis, it can be seen that the phase of the charged body in the 10kV high-voltage switchgear and the small air insulation gap between the phase and the ground are less than 125mm, resulting in an accident in capacity.
使用復(fù)合絕緣時,空氣間隙不應(yīng)忽視:
When using composite insulation, the air gap should not be ignored:
在一些10kV高壓開關(guān)柜中,安裝了一個由絕緣材料制成的隔板,形成一個帶電體。空氣間隙。絕緣隔板。復(fù)合絕緣模式,如接地體。從實際情況來看,使用這種復(fù)合絕緣,不能忽視空氣間隙,空氣間隙不小于30mm,否則很容易造成絕緣事故。
濟南電氣成套
In some 10kV high-voltage switchgear cabinets, a partition made of insulating material is installed to form a charged body. Air gap. Insulating partition. Composite insulation mode, such as grounding body. From the actual situation, using this composite insulation cannot ignore the air gap, which should not be less than 30mm, otherwise it is easy to cause insulation accidents.
接觸容量不足或接觸不良,引起開關(guān)柜發(fā)熱:
Insufficient contact capacity or poor contact, causing heating of the switchgear:
當(dāng)接觸點容量不足或接觸不良時,局部溫度升高,嚴重情況下,載流部分燒斷,導(dǎo)致地面或相間閃電弧,導(dǎo)致絕緣閃光絡(luò)。110kV變電站發(fā)生了——由于刀閘下樁發(fā)熱和燒斷,導(dǎo)致開關(guān)屏起火。爆炸事故。
When the capacity of the contact point is insufficient or the contact is poor, the local temperature increases. In severe cases, the current carrying part burns out, leading to ground or interphase lightning arcs and insulation flashover. A 110kV substation occurred - due to the heating and burning of the pile under the knife switch, the switch panel caught fire. Explosion accidents.
運行環(huán)境差,維修質(zhì)量低:
Poor operating environment and low maintenance quality:
通常情況下,10kV高壓開關(guān)柜的運行環(huán)境較差,經(jīng)常會受到灰塵、煙霧、蒸汽等因素的影響,導(dǎo)致絕緣層表面腐蝕,產(chǎn)生導(dǎo)電材料,形成絕緣缺陷。另外還有一些開關(guān)柜使用單位,不重視設(shè)備的維修。維修,不能及時發(fā)現(xiàn)和各種絕緣缺陷,終造成絕緣事故。
Usually, the operating environment of 10kV high-voltage switchgear is poor, and it is often affected by factors such as dust, smoke, steam, etc., resulting in corrosion of the insulation layer surface, the generation of conductive materials, and the formation of insulation defects. In addition, some switchgear users do not attach importance to equipment maintenance. Repair, failure to timely detect and eliminate various insulation defects, ultimately leading to insulation accidents.
附件絕緣性能差:
Poor insulation performance of accessories:
有許多10kV高壓開關(guān)柜的制造商。為了降低成本,一些制造商采用低絕緣水平的配套配件,降低了整個開關(guān)柜的污染閃電壓,不能滿足額定標(biāo)準要求。根據(jù)《6~10kV高壓開關(guān)柜選擇原則》,結(jié)合實際運行經(jīng)驗,附件沿表面絕緣爬電比不應(yīng)低于以下要求:瓷絕緣件18mm/kV,有機絕緣件
There are many manufacturers of 10kV high-voltage switchgear in China. In order to reduce costs, some manufacturers use matching accessories with low insulation levels to reduce the pollution flashover voltage of the entire switchgear, which cannot meet the rated standard requirements. According to the "Selection Principles for 6-10kV High Voltage Switchgear" and combined with practical operating experience, the creepage ratio of accessories along the surface insulation should not be lower than the following requirements: porcelain insulation parts 18mm/kV, organic insulation parts
本文由濟南電氣成套友情奉獻.更多有關(guān)的知識請點 http://www.26huojia.com 真誠的態(tài)度.為您提供為的服務(wù).更多有關(guān)的知識我們將會陸續(xù)向大家奉獻.敬請期待.